Enhancing Power System Observability: For Simultaneous Placement of PMUs and PFMs with Contingency Considerations

Jayanti Sarker*, Krishna Sarker**, Swapan Kumar Goswami***
* Department of Electrical Engineering, Techno Main Salt Lake, Kolkata, West Bengal, India.
** Department of Electrical Engineering, St. Thomas' College of Engineering & Technology, West Bengal, India.
*** Department of Electrical Engineering, Jadavpur University, West Bengal, India.
Periodicity:January - March'2024
DOI : https://doi.org/10.26634/jee.17.3.20684

Abstract

In this paper, a novel approach for the optimal placement of Phasor Measurement Units (PMUs) and Power Flow Measurement (PFM) devices is presented to ensure continuous observability of the power system network. The method incorporates the impact of contingency, specifically addressing the potential loss of a single PMU, in the optimal allocation strategy, thus ensuring full observability even under adverse conditions. To further optimize the deployment of monitoring devices, the concept of a zero-injection bus is introduced into the proposed technique, resulting in a reduced number of required PMUs and PFMs. Leveraging the Cuckoo Optimization Algorithm (COA), a heuristic technique is employed for the optimal location of these monitoring devices. The effectiveness and efficiency of the proposed method are validated through extensive testing on a 7-bus test system, IEEE-14, 57, and 118 bus test systems, as well as a real-world system. Comparative analysis with existing literature substantiates the superior performance of this approach.

Keywords

Contingency Analysis, Cybersecurity, Cuckoo Optimization Algorithm (COA), Heuristic Optimization, Observability, Phasor Measurement Units (PMUs), Power Flow Measurement (PFM), Power System Configuration, Power System Resilience, Power System Dynamics, Real-world Deployment, Scalability.

How to Cite this Article?

Sarker, J., Sarker, K., and Goswami, S. K. (2024). Enhancing Power System Observability: For Simultaneous Placement of PMUs and PFMs with Contingency Considerations. i-manager’s Journal on Electrical Engineering, 17(3), 55-66. https://doi.org/10.26634/jee.17.3.20684

References

If you have access to this article please login to view the article or kindly login to purchase the article

Purchase Instant Access

Single Article

North Americas,UK,
Middle East,Europe
India Rest of world
USD EUR INR USD-ROW
Pdf 35 35 200 20
Online 35 35 200 15
Pdf & Online 35 35 400 25

Options for accessing this content:
  • If you would like institutional access to this content, please recommend the title to your librarian.
    Library Recommendation Form
  • If you already have i-manager's user account: Login above and proceed to purchase the article.
  • New Users: Please register, then proceed to purchase the article.